A.5 Default Settings
307
7ST6 Manual
E50417-G1176-C251-A3
Interlocking
With blocks of level Interlocking (SFS_BEARB = interlocking), standard interlocking
for three switchgears (circuit breaker, disconnector and earth switch) is pre-defined.
Due to the large functional scope of the logic you will find this level on two worksheets.
The circuit breaker can only be closed if
• the circuit breaker is set to OPEN or CLOSE and
• the disconnector is set to OPEN or CLOSE and
• the earth switch is set to OPEN or CLOSE and
• the disconnector and the earth switch are not set to CLOSE at the same time and
• the input indication „CB wait“ is set to OPEN and
• the input indication „Door open“ is set to OPEN.
The disconnector can only be closed if:
• the circuit breaker is set to OPEN and
• the earth switch is set to OPEN and
• the disconnector is set to OPEN or CLOSE and
• the input indication „Door open“ is set to OPEN.
The disconnector can only be opened if:
• the circuit breaker is set to OPEN and
• the disconnector is set to OPEN or CLOSE and
• the earth switch is set to OPEN or CLOSE and
• the input indication„Door open“ is set to OPEN.
The earth switch can only be closed if:
• the circuit breaker is set to OPEN and
• the disconnector is set to OPEN and
• the earth switch is set to OPEN or CLOSE and
• the input indication „Door open“ is set to OPEN.
If the above requirements are not fulfilled, the actions of the switch commands will be
blocked with error messages by DIGSI
®
.