A.8 Settings
317
7ST6 Manual
E50417-G1176-C251-A3
1387
GAMMA ZOR
Distance prot.
-70 .. 40
°
-20
°
Angle Limit. Gamma Overreach
Zone
1388
ROR Reverse
Distance prot.
1A
0.20 .. 250.00
Ω
10.00
Ω
Resistance R Overreach Zone
Reverse
5A
0.04 .. 50.00
Ω
2.00
Ω
1389
XOR Reverse
Distance prot.
1A
0.20 .. 250.00
Ω
20.00
Ω
Reactance X Overreach Zone
Reverse
5A
0.04 .. 50.00
Ω
4.00
Ω
1390
ZOR Reverse
Distance prot.
1A
0.20 .. 250.00
Ω
20.00
Ω
Impedance Z Overreach Zone
Reverse
5A
0.04 .. 50.00
Ω
4.00
Ω
2301
Inrush DIS >=Z2
Distance prot.
InRushRestraint
NO
YES
NO
Distance Zones >=Z2 Blocked by
Inrush
2302
Inrush O/C
InRushRestraint
Overcurrent
NO
YES
NO
O/C Blocked by Inrush
2303
Inrush O/C BU
InRushRestraint
Emerg. O/C
NO
YES
NO
Emerg. O/C Blocked by Inrush
2305
2nd HARM.BLOCK
InRushRestraint
10 .. 45 %
15 %
2nd Harmonics Content of Inrush
Blocking
2306
Imax InrushRest
InRushRestraint
1A
0.5 .. 25.0 A
7.5 A
Max.Current, overriding inrush
restraint
5A
2.5 .. 125.0 A
37.5 A
2307
SI Time INRUSH
InRushRestraint
0 .. 10000 ms;
∞
∞
ms
Seal-In Time of Inrush Detection
2401
HS O/C
HS O/C
ON
OFF
ON
High-Speed Overcurrent Protec-
tion
2404
I HS O/C
HS O/C
1A
1.0 .. 25.0 A;
∞
10.0 A
High-Speed O/C Pickup Current
5A
5 .. 125 A;
∞
50 A
2405
T HS O/C
HS O/C
0.006 .. 0.100 sec; 0;
∞
0.000 sec
High-Speed O/C Delay Time
2408
HS O/C TRIP
HS O/C
single-channel
dual-channel
dual-channel
HS O/C TRIP Allocation
2601
OverCurrent
Overcurrent
ON
OFF
OFF
Overcurrent Protection Function
2602
CURVE O/C
Overcurrent
Definite Time
TOC ANSI
TOC IEC
Definite Time
Characteristic Curve for O/C
2603
O/C SOTF Trip
Overcurrent
YES
NO
NO
Instantan. Trip after Switch-onto-
Fault
2605
I>>>
Overcurrent
1A
0.10 .. 25.00 A;
∞
4.00 A
Pickup Current I>>> VeryHigh-
SetStage
5A
0.50 .. 125.00 A;
∞
20.00 A
2606
T I>>>
Overcurrent
0.00 .. 30.00 sec;
∞
0.10 sec
Delay Time T I>>> Very High Set
Stage
2608
I>>
Overcurrent
1A
0.10 .. 25.00 A;
∞
2.00 A
I>> Pickup
5A
0.50 .. 125.00 A;
∞
10.00 A
2609
T I>>
Overcurrent
0.00 .. 30.00 sec;
∞
0.30 sec
T I>> Time Delay
2611
IEC Curve
Overcurrent
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
2612
ANSI Curve
Overcurrent
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
2614
I>
Overcurrent
1A
0.10 .. 25.00 A;
∞
1.50 A
I> Pickup
5A
0.50 .. 125.00 A;
∞
7.50 A
2615
T I>
Overcurrent
0.00 .. 30.00 sec;
∞
0.50 sec
T I> Time Delay
2617
IP
Overcurrent
1A
0.10 .. 4.00 A;
∞
1.00 A
Pickup Current IP for IEC
5A
0.50 .. 20.00 A;
∞
5.00 A
2618
T IP
Overcurrent
0.05 .. 3.00 sec;
∞
0.50 sec
Time Dial T IP for IEC
2619
D IP
Overcurrent
0.50 .. 15.00 ;
∞
5.00
Time Dial D IP for ANSI
2701
Emerg. O/C
Emerg. O/C
ON
OFF
ON
Emergency Overcurrent Func-
tion
2702
SOTF Emerg. O/C
Emerg. O/C
NO
YES
NO
Instantan. trip after Switch-onto-
Fault
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments