A.8 Settings
319
7ST6 Manual
E50417-G1176-C251-A3
3501
FCT Synchronism
Sync. Check
ON
OFF
ON
Synchronism and Voltage Check
function
3502
Dead Volt. Thr.
Sync. Check
1 .. 60 V
5 V
Voltage Threshold Dead Line /
Reference
3503
Live Volt. Thr.
Sync. Check
20 .. 125 V
90 V
Voltage Threshold Live Line /
Reference
3504
Umax
Sync. Check
20 .. 140 V
110 V
Maximum permissible voltage
3507
T-SYN. DURATION
Sync. Check
0.01 .. 600.00 sec;
∞
1.00 sec
Maximum duration of synchro-
nism-check
3508
T SYNC-STAB
Sync. Check
0.00 .. 30.00 sec
0.00 sec
Synchronous condition stability
timer
3509
SyncSD
Sync. Check
(Setting options depend
on configuration)
None
synchronizable switching device
3510
Op.mode with AR
Sync. Check
with T-CB close
w/o T-CB close
w/o T-CB close
Operating mode with AR
3511
Max. Volt. Diff
Sync. Check
1.0 .. 50.0 V
2.0 V
Maximum voltage difference
3512
Max. Freq. Diff
Sync. Check
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
3513
Max. Angle Diff
Sync. Check
1 .. 80
°
10
°
Maximum angle difference
3515A
SYNC-CHECK
Sync. Check
YES
NO
YES
Live Ref. / Live Line and Sync
3516
Uref>Uline<
Sync. Check
YES
NO
NO
Live Ref. / Dead Line Check
3517
Uref<Uline>
Sync. Check
YES
NO
NO
Dead Ref. / Live Line Check
3518
Uref<Uline<
Sync. Check
YES
NO
NO
Dead Ref. / Dead Line Check
3519
OVERRIDE
Sync. Check
YES
NO
NO
Override of any check before AR
3530
Op.mode with MC
Sync. Check
with T-CB close
w/o T-CB close
w/o T-CB close
Operating mode with Man.Cl
3531
MC maxVolt.Diff
Sync. Check
1.0 .. 50.0 V
2.0 V
Maximum voltage difference
3532
MC maxFreq.Diff
Sync. Check
0.01 .. 2.00 Hz
0.10 Hz
Maximum frequency difference
3533
MC maxAngleDiff
Sync. Check
1 .. 80
°
10
°
Maximum angle difference
3535A
MC SYNCHR
Sync. Check
YES
NO
YES
Live Ref. / Live Line and Sync
before MC
3536
MC Uref>Uline<
Sync. Check
YES
NO
NO
Live Ref. / Dead Line Check
before MC
3537
MC Uref<Uline>
Sync. Check
YES
NO
NO
Dead Ref. / Live Line Check
before MC
3538
MC Uref<Uline<
Sync. Check
YES
NO
NO
Dead Ref. / Dead Line Check
before MC
3539
MC O/RIDE
Sync. Check
YES
NO
NO
Override of any check before
Man.Cl
3701
OVERVOLTAGE
Over/Under Volt
ON
OFF
ON
Overvoltage Protection
3702
U>>
Over/Under Volt
20 .. 170 V;
∞
150 V
Pickup Overvoltage U>>
3703
U>> Reset
Over/Under Volt
0.50 .. 0.95
0.95
Reset Ratio U>>
3704
T U>>
Over/Under Volt
0.00 .. 60.00 sec;
∞
1.00 sec
Delay Time Overvoltage U>>
3705
U>
Over/Under Volt
20 .. 170 V;
∞
120 V
Pickup Overvoltage U>
3706
U> Reset
Over/Under Volt
0.50 .. 0.95
0.95
Reset Ratio U>
3707
T U>
Over/Under Volt
0.00 .. 60.00 sec;
∞
2.00 sec
Delay Time Overvoltage U>
3711
UNDERVOLTAGE
Over/Under Volt
ON
OFF
ON
Undervoltage Protection
3712
U<<
Over/Under Volt
20 .. 120 V; 0
30 V
Pickup Undervoltage U<< (pos.
seq.)
3713
T U<<
Over/Under Volt
0.00 .. 60.00 sec;
∞
1.00 sec
Delay Time Undervoltage U<<
3715
U<
Over/Under Volt
20 .. 120 V; 0
70 V
Pickup Undervoltage U< (pos.
seq.)
3716
T U<
Over/Under Volt
0.00 .. 60.00 sec;
∞
2.00 sec
Delay Time Undervoltage U<
3802
START
Fault Locator
TRIP
Reclosing/Trip
TRIP
Start fault locator with
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments