2 Functions
82
7ST6 Manual
E50417-G1176-C251-A3
2.3.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2302
Inrush O/C
NO
YES
NO
O/C Blocked by Inrush
2601
OverCurrent
ON
OFF
OFF
Overcurrent Protection
Function
2602
CURVE O/C
Definite Time
TOC ANSI
TOC IEC
Definite Time
Characteristic Curve for
O/C
2603
O/C SOTF Trip
YES
NO
NO
Instantan. Trip after
Switch-onto-Fault
2605
I>>>
1A
0.10 .. 25.00 A;
∞
4.00 A
Pickup Current I>>> Very-
HighSetStage
5A
0.50 .. 125.00 A;
∞
20.00 A
2606
T I>>>
0.00 .. 30.00 sec;
∞
0.10 sec
Delay Time T I>>> Very
High Set Stage
2608
I>>
1A
0.10 .. 25.00 A;
∞
2.00 A
I>> Pickup
5A
0.50 .. 125.00 A;
∞
10.00 A
2609
T I>>
0.00 .. 30.00 sec;
∞
0.30 sec
T I>> Time Delay
2611
IEC Curve
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
2612
ANSI Curve
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
2614
I>
1A
0.10 .. 25.00 A;
∞
1.50 A
I> Pickup
5A
0.50 .. 125.00 A;
∞
7.50 A
2615
T I>
0.00 .. 30.00 sec;
∞
0.50 sec
T I> Time Delay
2617
IP
1A
0.10 .. 4.00 A;
∞
1.00 A
Pickup Current IP for IEC
5A
0.50 .. 20.00 A;
∞
5.00 A
2618
T IP
0.05 .. 3.00 sec;
∞
0.50 sec
Time Dial T IP for IEC
2619
D IP
0.50 .. 15.00 ;
∞
5.00
Time Dial D IP for ANSI