2.6 Overvoltage and Undervoltage Protection
93
7ST6 Manual
E50417-G1176-C251-A3
2.6.4
Settings
2.6.5
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
3701
OVERVOLTAGE
ON
OFF
ON
Overvoltage Protection
3702
U>>
20 .. 170 V;
∞
150 V
Pickup Overvoltage U>>
3703
U>> Reset
0.50 .. 0.95
0.95
Reset Ratio U>>
3704
T U>>
0.00 .. 60.00 sec;
∞
1.00 sec
Delay Time Overvoltage U>>
3705
U>
20 .. 170 V;
∞
120 V
Pickup Overvoltage U>
3706
U> Reset
0.50 .. 0.95
0.95
Reset Ratio U>
3707
T U>
0.00 .. 60.00 sec;
∞
2.00 sec
Delay Time Overvoltage U>
3711
UNDERVOLTAGE
ON
OFF
ON
Undervoltage Protection
3712
U<<
20 .. 120 V; 0
30 V
Pickup Undervoltage U<< (pos.
seq.)
3713
T U<<
0.00 .. 60.00 sec;
∞
1.00 sec
Delay Time Undervoltage U<<
3715
U<
20 .. 120 V; 0
70 V
Pickup Undervoltage U< (pos.
seq.)
3716
T U<
0.00 .. 60.00 sec;
∞
2.00 sec
Delay Time Undervoltage U<
No.
Information
Type of In-
formation
Comments
4331
U> Detection
OUT
Overvoltage detection : Stage U>
4332
U>> Detection
OUT
Overvoltage detection : Stage U>>
4335
U> Trip
OUT
Overvoltage trip : Stage U>
4336
U>> Trip
OUT
Overvoltage trip : Stage U>>
13830
OVER. OFF
OUT
Overvoltage Protection is switched off
13832
UNDER. OFF
OUT
Undervoltage Protection is switched off
13834
OVER/UNDER PU
OUT
Over/Undervoltage Protection picked up
13835
UNDER U< PU
OUT
Undervolt. U< picked up
13836
UNDER U<< PU
OUT
Undervolt. U<< picked up
13837
UNDER U< TRIP
OUT
Undervolt. U< TRIP command
13838
UNDER U<< TRIP
OUT
Undervolt. U<< TRIP command
13839
OVER/UNDER TRIP
OUT
Over/Undervoltage Prot. TRIP comm.