2 Functions
192
7ST6 Manual
E50417-G1176-C251-A3
2.19.3 Statistics
The number of trips initiated by 7ST6, the accumulated interrupted currents resulting
from trips initiated by protection functions and the number of close commands initiated
by the auto-reclosure function are counted.
2.19.3.1 Functional Description
Counters and Mem-
ories
The counters and memories of the statistics are saved by the device. Therefore the
information will not get lost in case the auxiliary voltage supply fails. The counters,
however, can be reset back to zero or to any value within the setting range.
Switching statistics can be viewed on the LCD of the device, or on a PC running
DIGSI
®
and connected to the operating or service interface.
A password is not required to read counter and stored values but is required to change
or delete them. You will find more details in the SIPROTEC
®
4 System Description
(Order No. E50417-H1176-C151).
Number of Trips
The number of trips initiated by the device 7ST6 are counted.
Number of Auto-
matic Reclosing
Commands
If the device is equipped with the integrated automatic reclosure, the automatic close
commands are also counted separately for the first reclosure cycle and other reclo-
sure cycles.
Interrupted Cur-
rents
Following each trip command the device registers the value of each current phase that
was switched off. This information is then provided in the trip log and summated in a
register. The maximum interrupted current that was switched off is stored as well. The
specified measured values are primary values.
For the last trip, the value of the current-time integral and the squared current-time in-
tegral I
2
t are output and separately summated.