3.1 Mounting and Connections
233
7ST6 Manual
E50417-G1176-C251-A3
Figure 3-17
Example of panel flush mounting of a device (housing size
1
/
1
)
3.1.3.2
Rack and Cubicle Mounting
2 mounting brackets are required for incorporating a device in a rack or cubicle. The
order number is given in the Appendix, Subsection A.1.
For the
1
/
2
housing size (Figure 3-18), there are four covers and four holes. For the
1
/
1
housing size (Figure 3-19) there are six covers and six holes.
• First the two mounting brackets in the rack or cubicle are screwed loosely by means
of 4 screws each.
• Remove the 4 covers at the corners of the front cover, for size
1
/
1
the two covers
located centrally at the top and bottom also have to be removed. Thus the 4 respec-
tively 6 elongated holes in the mounting flange are revealed and can be accessed.
• Fasten the device to the mounting brackets with four or six screws.
• Mount the four or six covers.
• Next, tighten the 8 screws of the mounting brackets in the frame or cabinet.
• Connect the low-resistance operational and protective earth on the rear plate of the
device, using at least one M4 screw for the device earthing. The cable cross-section
used must correspond to the largest connected cable cross-section, at least being
2.5 mm
2
(AWG 14).
• Establish connections via the plug-in or screw connections on the rear panel of the
housing according to circuit diagram.
For screw connections with forked lugs or direct connection, before inserting wires
the screws must be tightened so that the screw heads are flush with the outer edge
of the connection block.
A ring lug must be centred in the connection chamber in such a way that the screw
thread fits in the hole of the lug.
Specifications regarding maximum cross sections, tightening torques, bending radii
and tension relief as specified in the SIPROTEC
®
4 System Description (Order No.
E50417-H1176-C151) must be observed. You will find hints in the short description
included in the device.