E50417-G1176-C251-A3
Vibration and Shock Stress During Transport
4.1.7
Climatic Stress Tests
Climatic tests
Humidity
Standards:
IEC 60255-21 and IEC 60068
Oscillation
IEC 60255-21-1, Class 2
IEC 60068-2-6
Sinusoidal
5 Hz to 8 Hz:
±
7.5 mm amplitude;
8 Hz to 150 Hz: 2 g acceleration sweep rate 1 octave/min
20 cycles in 3 orthogonal axes
Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
Semi-sinusoidal
15 g acceleration, duration 11 ms,
3 shocks each in both directions of the 3 axes
Continuous shock
IEC 60255-21-2, Class 1
IEC 60068-2-29
Semi-sinusoidal
10 g acceleration, duration 16 ms,
1000 shocks each in both directions of the 3 axes
Standards:
IEC 60255-6
Type tested (acc. IEC 60086-2-1 and -2, Test Bd, for 16
h)
–23
°
F to +85
°
C (-25
°
C bis +40
°
C)
Limiting temporary (transient) operating temperature
(tested for 96 h)
–4
°
F to +158
°
F or –20
°
C to +70
°
C (legibility of display may
be restricted from +131
°
F or +55
°
C)
Recommended for permanent operation (according to
IEC 60255-6)
–23
°
F to +55
°
C (–5
°
C bis +40
°
C)
Limit Temperatures for Storage
–23
°
F to +55
°
C (-25
°
C bis +40
°
C)
Limit Temperatures during Transport
–23
°
F to +70
°
C (-25
°
C bis +40
°
C)
STORE AND TRANSPORT OF THE DEVICE WITH FACTORY PACKAGING!
Limit temperatures for normal operation (i.e. output
relays not energized)
–23
°
F to +70
°
C (-20
°
C bis +40
°
C)
Limit temperatures under maximum load (max. cont.
admissible input and output values)
-5
°
C to +55
°
C
Permissible humidity
Annual average
≤
75 % relative humidity;
On 56 days of the year up to 93% relative humidity. Conden-
sation must be avoided in operation!