2.1 General
31
7ST6 Manual
E50417-G1176-C251-A3
2.1.2.4
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
2.1.2.5
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
610
FltDisp.LED/LCD
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
615
Spont. FltDisp.
NO
YES
YES
Spontaneous display of flt.annun-
ciations
620
T Backlight on
1 .. 1000 min
60 min
Time Backlight on
699A
TO IV-Bit T103
0 .. 1500 min
1380 min
Timeout IV-Bit T103
No.
Information
Type of In-
formation
Comments
-
Test mode
IntSP
Test mode
-
DataStop
IntSP
Stop data transmission
-
SynchClock
IntSP_Ev
Clock Synchronization
-
>Light on
SP
>Back Light on
-
HWTestMod
IntSP
Hardware Test Mode
-
Error FMS1
OUT
Error FMS FO 1
-
Error FMS2
OUT
Error FMS FO 2
-
Brk OPENED
IntSP
Breaker OPENED
-
FdrEARTHED
IntSP
Feeder EARTHED
1
Not configured
SP
No Function configured
2
Non Existent
SP
Function Not Available
3
>Time Synch
SP
>Synchronize Internal Real Time Clock
5
>Reset LED
SP
>Reset LED
15
>Test mode
SP
>Test mode
16
>DataStop
SP
>Stop data transmission
51
Device OK
OUT
Device is Operational and Protecting
55
Reset Device
OUT
Reset Device
56
Initial Start
OUT
Initial Start of Device
60
Reset LED
OUT_Ev
Reset LED
67
Resume
OUT
Resume
68
Clock SyncError
OUT
Clock Synchronization Error
69
DayLightSavTime
OUT
Daylight Saving Time
70
Settings Calc.
OUT
Setting calculation is running
71
Settings Check
OUT
Settings Check
72
Level-2 change
OUT
Level-2 change
73
Local change
OUT
Local setting change
110
Event Lost
OUT_Ev
Event lost
113
Flag Lost
OUT
Flag Lost
125
Chatter ON
OUT
Chatter ON
140
Error Sum Alarm
OUT
Error with a summary alarm