A.8 Settings
311
7ST6 Manual
E50417-G1176-C251-A3
A.8
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
201
CT Starpoint
P.System Data 1
towards Line
towards Busbar
towards Line
CT Starpoint
202
CT PRIMARY
P.System Data 1
10 .. 5000 A
1000 A
CT Rated Primary Current
203
CT SECONDARY
P.System Data 1
1A
5A
1A
CT Rated Secondary Current
204
Unom PRIMARY
P.System Data 1
1.0 .. 150.0 kV
15.0 kV
Rated Primary Voltage
205
Unom SECONDARY
P.System Data 1
50.0 .. 130.0 V
100.0 V
Rated Secondary Voltage (Ph-
Ph)
206
IF CT STARPOINT
P.System Data 1
towards Line
towards Busbar
towards Line
IF CT Starpoint
207
IF CT PRIMARY
P.System Data 1
10 .. 5000 A
1000 A
CT Rated Primary Current IF
209
UF PRIMARY
P.System Data 1
1.0 .. 150.0 kV
15.0 kV
Rated Primary Voltage UF
210
UF SECONDARY
P.System Data 1
50.0 .. 130.0 V
100.0 V
Rated Secondary Voltage UF
211
IX CT STARPOINT
P.System Data 1
towards Line
towards Busbar
towards Line
IX CT Starpoint
212
IX CT PRIMARY
P.System Data 1
10 .. 5000 A
1000 A
CT Rated Primary Current IX
213
CURRENT I1, I2
P.System Data 1
Separate I1, I2
Sum I1, I2
Separate I1, I2
Current Inputs I1, I2
215
Uline/Uref
P.System Data 1
0.50 .. 2.00
1.00
Matching Ratio Uline / Uref
230
Rated Frequency
P.System Data 1
50 Hz
60 Hz
25 Hz
16,7 Hz
50 Hz
Rated Frequency
234
No. SECTIONS
P.System Data 1
1 Section
2 Sections
3 Sections
4 Sections
5 Sections
without
1 Section
Number of Line Sections
235
No.SECTIONS REV
P.System Data 1
1 Section
2 Sections
3 Sections
4 Sections
5 Sections
without
without
Number of Line Sections
Reverse
236
Distance Unit
P.System Data 1
km
Miles
km
Distance measurement unit
237
T CB BREAKTIME
P.System Data 1
0.001 .. 0.600 sec
0.080 sec
Breaktime (Circuit Breaker)
238
T CB OPENING
P.System Data 1
0.001 .. 0.200 sec
0.030 sec
Opening Time (Circuit Breaker)
239
T-CB close
P.System Data 1
0.01 .. 0.60 sec
0.06 sec
Closing (operating) time of CB
240A
TMin TRIP CMD
P.System Data 1
0.01 .. 32.00 sec
0.15 sec
Minimum TRIP Command Dura-
tion
241A
TMax CLOSE CMD
P.System Data 1
0.01 .. 32.00 sec
1.00 sec
Maximum Close Command Du-
ration
242
T-CBtest-dead
P.System Data 1
0.10 .. 30.00 sec
0.10 sec
Dead Time for CB test-autoreclo-
sure
243
TEST CB CIRCUIT
P.System Data 1
Main Trip
Backup Trip
Both
Main Trip
Trip Circuit Test
245
BI CONTROL
P.System Data 1
Edge
Level
Edge
Control of BI for Changeover
Functions
251
BkrClosed I MIN
P.System Data 1
1A
0.04 .. 1.00 A
0.04 A
Closed Breaker Min. Current
Threshold
5A
0.20 .. 5.00 A
0.20 A
260
Ir-CB
P.System Data 1
10 .. 50000 A
1250 A
Rated Normal Current (Circuit
Breaker)