2 Functions
46
7ST6 Manual
E50417-G1176-C251-A3
2.1.6.3
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
2.1.6.4
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
402A
WAVEFORMTRIGGE
R
Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup
Waveform Capture
403A
WAVEFORM DATA
Fault event
Pow.Sys.Flt.
Fault event
Scope of Waveform Data
410
MAX. LENGTH
0.30 .. 5.00 sec
1.00 sec
Max. length of a Waveform
Capture Record
411
PRE. TRIG. TIME
0.05 .. 0.50 sec
0.10 sec
Captured Waveform Prior to
Trigger
412
POST REC. TIME
0.05 .. 0.50 sec
0.10 sec
Captured Waveform after Event
415
BinIn CAPT.TIME
0.10 .. 5.00 sec;
∞
0.50 sec
Capture Time via Binary Input
No.
Information
Type of In-
formation
Comments
-
FltRecSta
IntSP
Fault Recording Start
4
>Trig.Wave.Cap.
SP
>Trigger Waveform Capture
www