2.3 Overcurrent Protection
77
7ST6 Manual
E50417-G1176-C251-A3
Figure 2-14
Pick-up and tripping logic of the definite time overcurrent stages
Figure 2-14 shows the logic diagram of the definite-time overcurrent stages.
The function block „Switch onto fault“ is common to all stages. The parameter
O/C
SOTF Trip
(address
2603
) specifies whether instantaneous tripping of this stage via
the binary input
„>Manual Close“
(FNo. 356) is possible (
YES
) or not possible (
NO
).
Furthermore, all stages can be blocked by the inrush restraint function. This blocking
can be switched on (
YES
) or off (
NO
) in the parameter
Inrush O/C
. A blocking signal
generates the indication
„O/C Rush blk“
.