Functions
166
7UM62 Manual
C53000-G1176-C149-3
2.23.2.1 Settings of the Inverse Undervoltage Protection
2.23.2.2 Information for the Inverse Undervoltage Protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
4401
INV. UNDERVOLT.
OFF
ON
Block relay for trip com-
mands
OFF
Inverse Undervoltage Protec-
tion Up<
4402
Up< PICKUP
10.0..125.0 V
75.0 V
Up< Pickup
4403
T MUL
0.10..5.00 sec; 0
1.00 sec
Time Multiplier for Characteristic
4404
T Up<
0.00..60.00 sec;
∞
0.00 sec
T Up< Time Delay
F.No.
Alarm
Comments
06520 >BLOCK Up<
>BLOCK inverse undervoltage protection
06522 Up< OFF
Inv. Undervoltage prot. is switched OFF
06523 Up< BLOCK
Inv. Undervoltage protection is BLOCKED
06524 Up< ACTIVE
Inv. Undervoltage protection is ACTIVE
06525 Up< picked up
Inverse Undervoltage Up< picked up
06526 Up< ch. pick.up
Inv. Undervoltage Up<-char. picked up
06527 Up< AUS
Inverse Undervoltage Up< TRIP