Measured Value Monitoring Functions
251
7UM62 Manual
C53000-G1176-C149-3
2.38.2.2 Information of the Monitoring Functions
8109
SUM.Fact. U
0.60..0.95; 0
0.75
Factor for Volt. Sum. Monitoring
8110
Σ
I THRESHOLD S1
0.05..2.00 A
0.10 A
Summated Cur. Mon. Threshold
on Side 1
8111
Σ
I FACTOR S1
0.00..0.95
0.10
Summated Current Mon. Factor
on Side 1
8112
Σ
I THRESHOLD S2
0.05..2.00 A
0.10 A
Summated Cur. Mon. Threshold
on Side 2
8113
Σ
I FACTOR S2
0.00..0.95
0.10
Summated Current Mon. Factor
on Side 2
F.No.
Alarm
Comments
00161 Fail I Superv.
Failure: General Current Supervision
00230 Fail.
Σ
I Side1
Failure: Current Summation on Side 1
00231 Fail.
Σ
I Side2
Failure: Current Summation on Side 2
00571 Fail. Isym 1
Fail.: Current symm. supervision side 1
00572 Fail. Isym 2
Fail.: Current symm. supervision side 2
00164 Fail U Superv.
Failure: General Voltage Supervision
00165 Fail
Σ
U Ph-E
Failure: Voltage Summation Phase-Earth
00167 Fail U balance
Failure: Voltage Balance
00171 Fail Ph. Seq.
Failure: Phase Sequence
00265 FailPh.Seq I S1
Failure: Phase Sequence I side 1
00266 FailPh.Seq I S2
Failure: Phase Sequence I side 2
00176 Fail Ph. Seq. U
Failure: Phase Sequence Voltage
00197 MeasSup OFF
Measurement Supervision is switched OFF
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
00110 Event Lost
Event lost
00113 Flag Lost
Flag Lost
05010 >FFM BLOCK
>BLOCK fuse failure monitor
05011 >FFM U< extern
>FFM extern undervoltage
06575 VT Fuse Failure
Voltage Transformer Fuse Failure
00140 Error Sum Alarm
Error with a summary alarm
00181 Error A/D-conv.
Error: A/D converter
00210 Err1A/5AwrongS1
Err:1A/5Ajumper different from settingS1
00211 Err1A/5AwrongS2
Err:1A/5Ajumper different from settingS2