Auxiliary Functions
291
7UM62 Manual
C53000-G1176-C149-3
where
In addition, the protection functions calculate and provide the following measured
values:
Measured Values of
Rotor Earth Fault
Protection (Rn, fn)
The following secondary values are available: System-frequency displacement
voltage U
RE
(= U
E
), earth fault current I
RE
(= I
EE1
) and rotor earth resistance R
earth
,
total resistance R
tot
, total reactance X
tot
and phase angle
ϕ
Z
tot
of the total resistance
of the rotor earth fault protection.
Measured Values of
the Rotor Earth
Fault Protection
(1–3 Hz)
Frequency and amplitude of the 1–3 Hz generator (7XT71) f
gen
, U
gen
, current in the
rotor circuit I
gen
, charge at polarity reversal Q
C
and rotor earth resistance R
earth
.
Measured Values of
the Stator Earth
Fault Protection
(20 Hz)
Voltage and current in the stator earth circuit U
SEF
and I
SEF
, the specific stator earth
resistances R
sef
and R
sefp
(primary) and the phase angle
ϕ
SES between the current
and the voltage at 20 Hz.
Values of the
Differential
Protection
−
Differential and restraint currents (stabilized currents) I
Diff L1
, I
Diff L2
, I
Diff L3
, I
Stab L1
,
I
Stab L2
, I
Stab L3
, I–0
Diff
, I–0
Stab
, 3I0–1, 3I0–2 in percent of the nominal values of the
protected object. The phase angle of the three currents on both sides of the
protected object is
φ
IL1S1,
φ
IL2S1,
φ
IL3S1,
φ
IL1S2,
φ
IL2S2,
φ
IL3S2.
Thermal Measured
Values
− Θ
S
/
Θ
STrip
Overload protection measured values of the stator winding
depending on the phase, in % of the tripping overtemperature,
− Θ
S
/
Θ
STrip
L1
Normalized overload protection measured values of the stator
winding for phase L1
− Θ
S
/
Θ
STrip
L2
Normalized overload protection measured values of the stator
winding for phase L2
− Θ
S
/
Θ
STrip
L3
Normalized overload protection measured values of the stator
winding for phase L3
− Θ
R
/
Θ
Rmax
Normalized rotor temperature in % of the tripping temperature
−
T
Re.Inhib. time
Time until the next permissible restart
−
I
2 thermal
,
Rotor overtemperature due to the negative phase-sequence
component of the current, % of the tripping overtemperature,
Parameter
Address
Parameter
Address
0241