3 Installation and Commissioning
328
7UM62 Manual
C53000-G1176-C149-3
The rated current settings of the input current transformers are checked on the
C–I/O–2 board. All jumpers must be in the same position, i.e. there must be one
jumper each (X61 to X64) for each of the input transformers, and the common jumper
X60. However: In the version with sensitive earth fault current input (input transformer
T8) there is no jumper X64.
Jumpers X71, X72 and X73 on the C–I/O-2 board are used to set the bus address
and must not be changed. Table 3-11 shows the factory setting of the jumpers.
Table 3-11
Factory Jumper Setting on the C–I/O–2 Board
Jumper
Factory Setting
X71 (AD0)
1–2 (H)
X72 (AD1)
1–2 (H)
X73 (AD2)
2–3 (L)