4 Technical Data
454
7UM62 Manual
C53000-G1176-C149-3
In the following table, the amount of TICKS required by the individual elements of a
CFC chart is shown. A generic module refers to a module for which the number of in-
puts can be changed. Typical examples are the logic modules AND, NAND, OR, NOR.
Processing times in TICKS required by the individual elements
Setting Group
Switchover of the
Function
Parameters
Number of Available Setting Groups
2 (parameter group A and B)
Switchover Performed
Using the keypad
DIGSI
®
4 using the front operator interface
with protocol via system interface
using binary input
Run-Time Level
Limits in TICKS
MW_BEARB
(Measured value processing)
10000
PLC1_BEARB
(Slow PLC processing)
1900
PLC_BEARB
(Fast PLC processing)
200
SFS_BEARB
(
Interlocking)
10000
Individual Element
Amount of TICKS
Module, basic requirement
5
each input more than 3 inputs for generic modules
1
Connection to an input
6
Connection to an output signal
7
Additional for each configuration sheet
1