A.1 Ordering Information and Accessories
463
7UM62 Manual
C53000-G1176-C149-3
Measuring Functionalities
without extended measuring functionality
0
Min/Max values, energy counter
3
Protective Elements
Basic Generator Elements, included in all versions
A
Overcurrent protection with undervoltage seal in
(I> +U<)
ANSI 51
Overcurrent protection, directional
(I>>, dir.)
ANSI 50/51/67
Inverse time O/C protection
(t=f(I) +U<)
ANSI 51V
Thermal overload protection
(I
2
t)
ANSI 49
Negative sequence protection
(I
2
>, t=f(I
2
))
ANSI 46
Differential protection
(
∆
I)
ANSI 87G/87M/87T
Loss-of-field protection
(1/xd)
ANSI 40
Reverse power protection
(–P)
ANSI 32R
Forward power supervision
(P>, P<)
ANSI 32F
Undervoltage protection
(U<, t=f(U))
ANSI 27
Overvoltage protection
(U>)
ANSI 59
Frequency protection
(f<, f>)
ANSI 81
Overexitation (Volt/Hertz) protection
(U/f)
ANSI 24
Stator earth fault protection, non
–
directional, directional
((U
0
>, 3I
0
>,
∠
U
0
, 3I
0
)
ANSI 59N, 64G, 67G
Sensitive earth fault protection (also as rotor earth fault protection)
(I
EE
>)
ANSI 50/51GN, 64R
Rotor earth fault protection (fn, R measurement)
(R
E
<)
ANSI 64R (f
N
)
Motor starting time supervision
(I
an
2
t)
ANSI 48
Breaker failure protection
(I
min
>)
ANSI 50BF
Phase sequence supervision
(L
1
; L
2
; L
3
)
ANSI 47
4 external trip commands
(external trip)
---
Trip circuit monitoring
(TC mon.)
ANSI 74TC
Fuse failure monitor
((U
2
/U
1
; I
1
/I
2
)
ANSI 60FL
Threshold supervision
Standard Generator Protection, consisting of:
B
Basic Generator elements, + comprising:
Impedance protection
(Z<)
ANSI 21
100 % stator earth fault protection with 3rd harmonic
(U
0 (3. Harm.)
)
ANSI 59TN, 27TN3.H
Inadvertent energization protection
(I>, U<)
ANSI 50/27
Full Generator Protection, consisting of:
C
Standard Generator protection, + comprising:
Out-of-step protection
(
∆
Z/
∆
t)
ANSI 78 )
DC voltage/DC current protection
(Udc>)
ANSI 59N (DC)/51N (DC)
Startup overcurrent protection
(I>)
ANSI 51
Earth current differential protection
ANSI 87GN/TN
Asynchronous Motor Protection,consisting of:
F
Basic Generator Elements without underexcitation and overexitation
protection but with motor restart inhibit
(I
2
t)
ANSI 66, 49 Rotor
Transformer Protection,consisting of:
H
Basic Generator Protection, without underexcitation protection, unbalanced load protection and motor starting time supervision
Functionality/Additional Functions
without
A
Sensitive Rotor Earth Fault Protection
ANSI 64R (1 to 3 Hz)
B
(Square-wave voltage injection 1–3 Hz, Re<80 k
Ω)
and 100 % stator earth fault protection
ANSI 64G (100 %)
(Principle of 20 Hz voltage injection)
Earth Current Differential Protection
ANSI 87GN/TN
C
Network Decoupling (df/dt and vector jump)
ANSI 81R
E
All additional functions
G
Ordering example:
7UM6211–4EA99–0BA0 + L0B + M1K
here: Pos. 11 = 9 stands for L0B, i.e. version with Profibus DP system port on the rear optical, double ring
here: Pos. 12 = 9 stands for M1K, i.e. version with rear service port DIGSI 4, modem RS232 and
analog outputs 2 x (0 to 20 mA)
_
7UM62
7
8
13
15
14
_
9 10 11 12
Multifunctional Machine Protection
6
0