A Appendix
532
7UM62 Manual
C53000-G1176-C149-3
4006A U< DOUT RATIO
Undervoltage
Protection
1.01..1.20
1.05
U< Drop Out Ratio
4101
OVERVOLTAGE
Overvoltage
Protection
OFF
ON
Block relay for trip
commands
OFF
Overvoltage Protection
4102
U>
Overvoltage
Protection
30.0..170.0 V
115.0 V
U> Pickup
4103
T U>
Overvoltage
Protection
0.00..60.00 sec;
∞
3.00 sec
T U> Time Delay
4104
U>>
Overvoltage
Protection
30.0..170.0 V
130.0 V
U>> Pickup
4105
T U>>
Overvoltage
Protection
0.00..60.00 sec;
∞
0.50 sec
T U>> Time Delay
4106A U> DOUT RATIO
Overvoltage
Protection
0.90..0.99
0.95
U> Drop Out Ratio
4107A VALUES U>
Overvoltage
Protection
Voltage protection
with U-Phase-Phase
Voltage protection
with U-Phase-earth
Voltage protection
with U-Phase-Phase
Measurement Values for
U>
4201
O/U FREQUENCY
Frequency Pro-
tection
OFF
ON
Block relay for trip
commands
OFF
Over / Under Frequency
Protection
4202
f1 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
48.00 Hz
f1 Pickup
4203
f1 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
58.00 Hz
f1 Pickup
4204
T f1
Frequency Pro-
tection
0.00..600.00 sec
1.00 sec
T f1 Time Delay
4205
f2 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
47.00 Hz
f2 Pickup
4206
f2 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
57.00 Hz
f2 Pickup
4207
T f2
Frequency Pro-
tection
0.00..100.00 sec
6.00 sec
T f2 Time Delay
4208
f3 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
49.50 Hz
f3 Pickup
4209
f3 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
59.50 Hz
f3 Pickup
4210
T f3
Frequency Pro-
tection
0.00..100.00 sec
20.00 sec
T f3 Time Delay
4211
f4 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
52.00 Hz
f4 Pickup
4212
f4 PICKUP
Frequency Pro-
tection
40.00..65.00 Hz
62.00 Hz
f4 Pickup
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments