A.12 Settings
539
7UM62 Manual
C53000-G1176-C149-3
6602
IStart/IMOTnom
Restart Inhibit
for Motors
1.5..10.0
4.9
I Start / I Motor nominal
6603
T START MAX
Restart Inhibit
for Motors
3.0..320.0 sec
8.5 sec
Maximum Permissible Star-
ting Time
6604
T EQUAL
Restart Inhibit
for Motors
0.0..320.0 min
1.0 min
Temperature Equalization
Time
6606
MAX.WARM
STARTS
Restart Inhibit
for Motors
1..4
2
Permissible Number of
Warm Starts
6607
#COLD-#WARM
Restart Inhibit
for Motors
1..2
1
Number of Cold Starts -
Warm Starts
6608
K
τ
at STOP
Restart Inhibit
for Motors
1.0..100.0
5.0
Extension of Time Constant
at Stop
6609
K
τ
at RUNNING
Restart Inhibit
for Motors
1.0..100.0
2.0
Extension of Time Constant
at Running
6610
T MIN. INHIBIT
Restart Inhibit
for Motors
0.2..120.0 min
6.0 min
Minimum Restart Inhibit
Time
7001
BREAKER
FAILURE
Breaker Failure
Protection
OFF
ON
Block relay for trip
commands
OFF
Breaker Failure Protection
7002
TRIP INTERN
Breaker Failure
Protection
OFF
Start Breaker
Failure with
Bin.Outp.12
Start Breaker
Failure with CFC
OFF
Start with Internal TRIP
Command
7003
CIRC. BR. I>
Breaker Failure
Protection
0.04..2.00 A
0.20 A
Supervision Current Pickup
7004
TRIP-Timer
Breaker Failure
Protection
0.06..60.00 sec;
∞
0.25 sec
TRIP-Timer
7101
INADVERT. EN.
Inadvertent
Energisation
OFF
ON
Block relay for trip
commands
OFF
Inadvertent Energisation
7102
I STAGE
Inadvertent
Energisation
0.1..20.0 A;
∞
0.3 A
I Stage Pickup
7103
RELEASE U1<
Inadvertent
Energisation
10.0..125.0 V; 0
50.0 V
Release Threshold U1<
7104
PICK UP T U1<
Inadvertent
Energisation
0.00..60.00 sec;
∞
5.00 sec
Pickup Time Delay T U1<
7105
DROP OUT T U1<
Inadvertent
Energisation
0.00..60.00 sec;
∞
1.00 sec
Drop Out Time Delay T
U1<
7110
FltDisp.LED/LCD
Device
Display Targets on
every Pickup
Display Targets on
TRIP only
Display Targets on
every Pickup
Fault Display on LED / LCD
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments