A Appendix
544
7UM62 Manual
C53000-G1176-C149-3
9013
RTD 1 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 1: Temperature Stage
1 Pickup
9014
RTD 1 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 1: Temperature Stage
1 Pickup
9015
RTD 1 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 1: Temperature Stage
2 Pickup
9016
RTD 1 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 1: Temperature Stage
2 Pickup
9021A RTD 2 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 2: Type
9022A RTD 2 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 2: Location
9023
RTD 2 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 2: Temperature Stage
1 Pickup
9024
RTD 2 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 2: Temperature Stage
1 Pickup
9025
RTD 2 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 2: Temperature Stage
2 Pickup
9026
RTD 2 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 2: Temperature Stage
2 Pickup
9031A RTD 3 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 3: Type
9032A RTD 3 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 3: Location
9033
RTD 3 STAGE 1
RTD-Box
-50..250
°
C;
∞
100
°
C
RTD 3: Temperature Stage
1 Pickup
9034
RTD 3 STAGE 1
RTD-Box
-58..482
°
F;
∞
212
°
F
RTD 3: Temperature Stage
1 Pickup
9035
RTD 3 STAGE 2
RTD-Box
-50..250
°
C;
∞
120
°
C
RTD 3: Temperature Stage
2 Pickup
9036
RTD 3 STAGE 2
RTD-Box
-58..482
°
F;
∞
248
°
F
RTD 3: Temperature Stage
2 Pickup
9041A RTD 4 TYPE
RTD-Box
not connected
Pt 100 Ohm
Ni 120 Ohm
Ni 100 Ohm
not connected
RTD 4: Type
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments