Functions
70
7UM62 Manual
C53000-G1176-C149-3
2.10.2.2 Information for the Unbalanced Load Protection
1703
T WARN
0.00..60.00 sec;
∞
20.00 sec
Warning Stage Time Delay
1704
FACTOR K
2.0..100.0 sec;
∞
18.7 sec
Negativ Sequence Factor K
1705
T COOL DOWN
0..50000 sec
1650 sec
Time for Cooling Down
1706
I2>>
10..100 %
60 %
I2>> Pickup
1707
T I2>>
0.00..60.00 sec;
∞
3.00 sec
T I2>> Time Delay
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
05143 >BLOCK I2
>BLOCK I2 (Unbalance Load)
05146 >RM th.rep. I2
>Reset memory for thermal replica I2
05151 I2 OFF
I2 switched OFF
05152 I2 BLOCKED
I2 is BLOCKED
05153 I2 ACTIVE
I2 is ACTIVE
05158 RM th.rep. I2
Reset memory of thermal replica I2
05156 I2> Warn
Unbalanced load: Current warning stage
05165 I2> picked up
I2> picked up
05159 I2>> picked up
I2>> picked up
05160 I2>> TRIP
Unbalanced load: TRIP of current stage
05161 I2
Θ
TRIP
Unbalanced load: TRIP of thermal stage