Monitoring
Functions
On each polarity reversal, the charging current of the rotor earth capacitor is deter-
mined. A drop of this current allows to detect defects in the measurement circuit such
as wire breaks, poor brush contact etc. This is only possible, however, if the rotor-earth
capacitance is high enough (> 0.15 µF) and the interference from the excitation sys-
tem is low.
As an alternative, the protection function offers an external test option using a test re-
sistor (included in the 7XR6004 and 7XR6003). The test mode is activated via a binary
input, and the fault resistor is connected to a slip ring with an external relay. The pro-
tection function must be informed of the pertinent test resistance. The protection func-
tion issues appropriate indications showing the test results. It is also able to detect
one-sided interruptions (such as wire breaks or loose terminals in a coupling (see Fig-
ure 2-98)).
The evaluation logic is shown in Figure 2-100.