Functional Scope
23
7UM62 Manual
C53000-G1176-C149-3
2.2.2.1
Settings
Addr.
Setting Title
Setting Options
Default Setting
Comments
103
Grp Chge OPTION
Disabled
Enabled
Disabled
Setting Group Change Option
104
FAULT VALUE
Disabled
Instantaneous values
RMS values
Instantaneous
values
Fault values
105
DIFF. PROT.
Disabled
Enabled
Enabled
Differential Protection
106
PROT. OBJECT
Generator/Motor
3 phase Transformer
Generator/Motor
Protection Object
112
O/C PROT. I>
Disabled
Side 1
Side 2
Side 2
Overcurrent Protection I>
113
O/C PROT. I>>
Disabled
Non-Directional on side 1
Non-Directional on side 2
Directional on side 1
Directional on side 2
Non-Directional on
side 2
Overcurrent Protection I>>
114
O/C PROT. Ip
Disabled
with IEC-characteristic on
side 1
with ANSI-characteristic on
side 1
with IEC-characteristic on
side 2
with ANSI-characteristic on
side 2
Disabled
Inverse O/C Time Protection
116
Therm.Overload
Disabled
Enabled
Enabled
Thermal Overload Protection
117
UNBALANCE LOAD Disabled
Enabled
Enabled
Unbalance Load (Negative
Sequence)
118
O/C STARTUP
Disabled
Enabled
Enabled
Startup O/C protection
120
DIFF. PROT.
Disabled
Generator/Motor
3 phase Transformer
Generator/Motor
Differential Protection
121
REF PROT.
Disabled
Generator/Motor with IEE2
Generator/Motor with 3I0 of
Side 2
with Side 1 of Transformer
with Side 2 of Transformer
Disabled
Restricted earth fault protection
130
UNDEREXCIT.
Disabled
Enabled
Enabled
Underexcitation Protection
131
REVERSE POWER
Disabled
Enabled
Enabled
Reverse Power Protection
132
FORWARD
POWER
Disabled
Enabled
Enabled
Forward Power Supervision