Functions
34
7UM62 Manual
C53000-G1176-C149-3
2.3.2.2
List of Information
221
Unom PRIMARY
0.10..400.00 kV
6.30 kV
Rated Primary Voltage
222
Unom SECON-
DARY
100..125 V
100 V
Rated Secondary Voltage (Ph-
Ph)
223
UE CONNECTION
UE connected to neutral
transformer
UE connected to broken
delta winding
not connected
UE connected to any VT
UE connected to Rotor
UE connected to Loading
Resistor
UE connected to
neutral transformer
UE Connection
224
FACTOR UE
1.0..2500.0
36.4
VT Ratio Prim./Sec. Ue
225A
Uph / Udelta
1.00..3.00
1.73
Matching Ratio Ph.-VT to Bro-
ken-Delta-VT
280
TMin TRIP CMD
0.01..32.00 sec
0.15 sec
Minimum TRIP Command Dura-
tion
281
BkrClosed I MIN
0.04..1.00 A
0.04 A
Closed Breaker Min. Current
Threshold
295
TRANSDUCER 1
10 V
4-20mA
20mA
10 V
Transducer 1
296
TRANSDUCER 2
10 V
4-20mA
20mA
10 V
Transducer 2
297
TRANSDUCER 3
with filter
without filter
with filter
Transducer 3
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
05145 >Reverse Rot.
>Reverse Phase Rotation
05147 Rotation L1L2L3
Phase Rotation L1L2L3
05148 Rotation L1L3L2
Phase Rotation L1L3L2
00361 >FAIL:Feeder VT
>Failure: Feeder VT (MCB tripped)
05002 Operat. Cond.
Suitable measured quantities present