A.9 Default Settings
511
7UM62 Manual
C53000-G1176-C149-3
A.9
Default Settings
A.9.1
Binary Inputs
1
) for busbar connection
2
) 7UM622 only
A.9.2
Binary Outputs (output relays)
Binary input
Abbreviation
FNo
Type of
information
Description
Binary input 1
>SV tripped
5086
SP O/O
>Stop valve tripped
Binary input 2
>Uexc fail.
5328
SP
>Exc. voltage failure recognized
Binary input 3
>BLOCK f1
>BLOCK U<
>S/E/F Iee off
1
)
5206
6506
5176
1
)
SP O/O
SP O/O
1
)
SP
Generator circuit breaker open
1
)
Binary input 4
>FAIL:Feeder VT
>Useal-in BLK
>BLOCK U/V
0361
1950
6503
SP O/O
SP O/O
SP
Voltage transformer protective switch tripped
Binary input 5
>Ext trip 1
4526
SP O/O
External trip signal 1
Binary input 6
>Ext trip 1
4546
SP O/O
External trip signal 2
Binary input 7
>Trig.Wave.Cap.
0004
SP
>Trigger Waveform Capture
Binary input 8....15
2
)
List Empty
----
----
No functions configured (reserve)
Binary output
Abbreviation
FNo
Type
Description
Output relay 1
Error PwrSupply
Fail Battery
0147
0177
OUT O/O
OUT O/O
General indication: Internal monitoring
Output relay 2
Relay TRIP
0511
OUT O/O
Relay trip
Output relay 3
I> TRIP
Diff TRIP
Imp.Z1< TRIP
Imp.Z1B< TRIP
Imp.Z2< TRIP
Imp.T3> TRIP
I>> TRIP
O/C Ip TRIP
1815
5671
3977
3978
3979
3980
1809
1900
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
OUT O/O
Trip by short-circuit protection
Output relay 4
IEE>> TRIP
U0> TRIP
S/E/F TRIP
1223
5187
5193
OUT O/O
OUT O/O
OUT O/O
Trip by eartfault protection
Output relay 5
U< TRIP
U> TRIP
U>> TRIP
6539
6570
6573
OUT O/O
OUT O/O
OUT O/O
Trip by voltage protection
Output relay 6
f1 TRIP
f2 TRIP
5236
5237
OUT O/O
OUT O/O
Trip by frequency protection
Output relay 7
EXC<3 TRIP
Exc<U<TRIP
5343
5346
OUT O/O
OUT O/O
Trip by underexcitation protection