A Appendix
514
7UM62 Manual
C53000-G1176-C149-3
A.9.3
LED Indicators
A.9.4
Function Keys
LED
Abbreviation
FNo
Type of
information
Description
LED 1
Relay TRIP
0511
OUT O/O
Protective relay has tripped
LED 2
Relay PICKUP
0501
OUT O/O
Protective relay has picked up
LED 3
I> Fault L1
1811
OUT O/O
Fault L1
LED 4
I> Fault L2
1812
OUT O/O
Fault L2
LED 5
I> Fault L3
1813
OUT O/O
Fault L3
LED 6
IEE> TRIP
U0> TRIP
S/E/F TRIP
1226
5187
5193
OUT O/O
OUT O/O
OUT O/O
Earth fault
LED 7
Error PwrSupply
Fail Battery
0147
0177
OUT O/O
OUT O/O
Hardware failure
LED 8
Diff TRIP
5671
OUT O/O
Trip by differential protection
LED 9
Pr TRIP
Pr+SV TRIP
5097
5098
OUT O/O
OUT O/O
Trip by reverse power protection
LED 10
Exc<3 TRIP
Exc<1 TRIP
Exc<2 TRIP
Exc<U< TRIP
5343
5344
5345
5346
OUT O/O
OUT O/O
OUT O/O
OUT O/O
Trip by underexcitation protection
LED 11
I2>> TRIP
I2
Θ
TRIP
5160
5161
OUT O/O
OUT O/O
Trip by unbalanced protection
LED 12
f1 TRIP
f2 TRIP
f3 TRIP
5236
5237
5238
OUT O/O
OUT O/O
OUT O/O
Trip by overfrequency protection
LED 13
f4 TRIP
5239
OUT O/O
Trip by underfrequency protection
LED 14
U> TRIP
U>> TRIP
6570
6573
OUT O/O
OUT O/O
Trip by overvoltage protection
Function Key
Pre–settings
F1
Operating messages
F2
Operating measured values, primary
F3
Messages from the last eight network faults
F4
Jumping to the reset menu of the min/max values