A.12 Settings
523
7UM62 Manual
C53000-G1176-C149-3
A.12
Settings
NOTE: The following table lists all data which are available in the maximum complement of the device. De-
pendent on the ordered model, only those data may be present which are valid for the individual version.
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
201
STRPNT->OBJ S1
Power System
Data 1
YES
NO
YES
CT-Strpnt. Side1 in Direct.
of Object
202
IN-PRI I-SIDE1
Power System
Data 1
1..100000 A
500 A
CT Rated Primary Current
Side 1
203
IN-SEC I-SIDE1
Power System
Data 1
1A
5A
1A
CT Rated Secondary Cur-
rent Side 1
204
CT ANGLE W0
Power System
Data 1
-5.00..5.00
°
0.00
°
Correction Angle CT W0
205
FACTOR IEE1
Power System
Data 1
1.0..100000.0
60.0
CT Ratio Prim./Sec. IEE1
210
STRPNT->OBJ S2
Power System
Data 1
YES
NO
YES
CT-Strpnt. Side2 in Direct.
of Object
211
IN-PRI I-SIDE2
Power System
Data 1
1..100000 A
500 A
CT Rated Primary Current
Side 2
212
IN-SEC I-SIDE2
Power System
Data 1
1A
5A
1A
CT Rated Secondary Cur-
rent Side 2
213
FACTOR IEE2
Power System
Data 1
1.0..100000.0
60.0
CT Ratio Prim./Sec. IEE2
214
GRD TERM. IEE2
Power System
Data 1
Terminal Q7
Terminal Q8
Terminal Q7
Grounded Terminal CT
IEE2
221
Unom PRIMARY
Power System
Data 1
0.10..400.00 kV
6.30 kV
Rated Primary Voltage
222
Unom SECON-
DARY
Power System
Data 1
100..125 V
100 V
Rated Secondary Voltage
(Ph-Ph)
223
UE CONNECTION
Power System
Data 1
UE connected to
neutral transformer
UE connected to
broken delta win-
ding
not connected
UE connected to
any VT
UE connected to
Rotor
UE connected to
Loading Resistor
UE connected to
neutral transformer
UE Connection
224
FACTOR UE
Power System
Data 1
1.0..2500.0
36.4
VT Ratio Prim./Sec. Ue
225A
Uph / Udelta
Power System
Data 1
1.00..3.00
1.73
Matching Ratio Ph.-VT to
Broken-Delta-VT
241
UN-PRI SIDE 1
Power System
Data 1
0.40..800.00 kV
20.00 kV
Rated Primary Voltage Side
1