2 Functions
172
7UT613/63x Manual
C53000-G1176-C160-2
2.4.3
Time Overcurrent Protection for Residual Current
The function and operation of the definite-time overcurrent protection and of the
inverse-time overcurrent protection for residual current is discussed in detail in the
section „Time Overcurrent Protection - General“ above (see subsection 2.4.1). The fol-
lowing paragraphs contain the specific information for setting the overcurrent protec-
tion for residual current
3I0 O/C
.
2.4.3.1
Setting Notes
General
Note
The first time overcurrent protection for residual current is described in the setting in-
structions. The parameter addresses and message numbers of the second and third
time overcurrent protection are described at the end of the setting instructions under
„Additional Time Overcurrent Protection Functions for Residual Current“.
During configuration of the functional scope (section 2.1.3) the characteristic type for
the residual current stages is determined under address
122
DMT/IDMT 3I0
. Only
the settings for the characteristic selected can be performed here. The definite time
stages 3
I
0>> and 3
I
0> are available in all cases.
If a second or third residual overcurrent protection is used, this must be configured ac-
cordingly in addresses
134
DMT/IDMT 3I0 2
and
136
DMT/IDMT 3I0 3
.
Each protection function must be assigned to a side of the main protected object or
another 3-phase current measuring location. This can be carried out separately from
the phase overcurrent protection (section 2.1.4 under margin heading „Additional
Three-phase Protection Functions“). Consider also the assignment of the measured
current inputs of the device against the measuring locations (current transformer sets)
of the power plant (section 2.1.4 under margin heading „Assignment of 3-phase Mea-
suring Locations“).
Note
Note: If the time overcurrent protection is assigned to a side of the main protected
object, the current values are set referred to the rated current of that side I
I
/
I
NS
. In
other cases, current values are set in amps.
In address
2201
3I0 O/C
, the time overcurrent protection for residual current can be
set to
ON
or
OFF
. The option
Block relay
allows to operate the protection but the
trip output relay is blocked.
Address
2208
A
3I0 MAN. CLOSE
determines which of the zero sequence current
stages must be activated instantaneously with a detected manual close. Settings
3I0>> instant.
and
3I0> instant.
can be set independently from the selected
type characteristics;
3I0p instant.
is only possible if one of the inverse time stages
has been configured. The stabilisation does not affect
3I0>>
. This parameter can only
be set with DIGSI at
Additional Settings
. For this setting, similar considerations apply
as for the phase current stages.
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...