2 Functions
272
7UT613/63x Manual
C53000-G1176-C160-2
2.17.2 Setting Notes
General
Note
The first circuit breaker failure protection is described in the setting instructions. The
parameter addresses and message numbers of the second circuit breaker failure pro-
tection are described at the end of the setting instructions under „Additional Circuit
Breaker Failure Protection Functions“.
The circuit-breaker failure protection is only effective and accessible if address
170
=
BREAKER FAILURE
Enabled
is set during configuration. In case of single-
phase busbar protection no circuit-breaker failure protection is possible.
If the second circuit-breaker failure protection is used, this must be set under address
171
BREAKER FAIL. 2
to
Enabled
.
When assigning the protection functions (section 2.1.4 under margin heading „Addi-
tional 3-phase Protection Functions“, it was determined under address
470
BREAKER
FAIL.AT
at which side or measuring location of the protected the circuit-breaker
failure protection must be active. Please ensure that the side or measuring location of
the current and the monitored circuit breaker belong together! Both must be at the
supply side of the protected object.
For the second circuit-breaker failure protection the respective address
471
BREAKER
FAIL2AT
applies.
Under address
7101
BREAKER FAILURE
the first circuit-breaker failure protection
ON
or
OFF
is set. The option
Block relay
allows to operate the protection but the trip
output relay is blocked.
The second breaker failure protection is switched at address 7101
BREAKER
FAILURE
ON
or
OFF
.
Initiation
Three statements are essential for the correct initiation of the circuit breaker failure
protection:
The Current-flow MonitoringCurrent flow monitoring ensures that the current flow
stops after the trip command has been issued to the breaker to be monitored. It uses
the values set in the General Power System Data 2 is decisive (see section 2.1.6.1
under margin heading „Circuit Breaker Status“). The decisive value is the setting as-
signed to the side or measuring location that indicates the current of the monitored
circuit breaker (addresses
1111
to
1125
). This value will certainly be undershot in
case of an open circuit breaker.
The assignment of the CB auxiliary contacts or the CB feed-back information was ex-
ecuted in accordance with section 2.1.4 under „Circuit-breaker Data“. The configura-
tion of the respective binary inputs must be complete.
The tripping command for the monitored breaker is determined by address
7111
or
7112
START WITH REL.
(depending on the version of the device). Choose the
number of the output relay which shall trip the breaker to be monitored. If
START WITH
REL.
is parameterised on 0 , no initiation occurs via the internal binary output. Since
7UT613/63x will normally trip several circuit breakers by the various protection func-
tions, the device must be informed about which trip command is decisive for the initi-
ation of the breaker failure protection. If the breaker failure protection is intended to be
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...