2 Functions
286
7UT613/63x Manual
C53000-G1176-C160-2
spective measuring location or side (in case of earth faults, below the smallest fault
current). This parameter can only be altered in DIGSI at
Additional Settings
.
In address
8403
FUSE FAIL MON.
the fuse-failure monitor, in case of asymmetrical
tests, for example can be switched
off
.
Three-phase Mea-
sured Voltage
Failure (Fuse-
failure Monitor)
At address
8426
FFM U<max (3ph)
the minimum voltage is set. If the measured
voltage drops below this threshold and a simultaneous current jump is not detected
while all three-phase currents are greater than the minimum current required for the
impedance measurement by the distance protection according to (addresses
1111
to
1142
) a three-phase measured voltage failure is recognised. This parameter can only
be set with DIGSI at
Additional Settings
.
2.19.1.5 Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
8101
BALANCE I
ON
OFF
OFF
Current Balance Supervi-
sion
8102
BALANCE U
ON
OFF
OFF
Voltage Balance Supervi-
sion
8104
SUMMATION U
ON
OFF
OFF
Voltage Summation Su-
pervision
8105
PHASE ROTAT. I
ON
OFF
OFF
Current Phase Rotation
Supervision
8106
PHASE ROTAT. U
ON
OFF
OFF
Voltage Phase Rotation
Supervision
8111
BAL. I LIMIT M1
1A
0.10 .. 1.00 A
0.50 A
Current Balance Monitor
Meas. Loc. 1
5A
0.50 .. 5.00 A
2.50 A
8112
BAL. FACT. I M1
0.10 .. 0.90
0.50
Bal. Factor for Curr.
Monitor Meas.Loc.1
8113A
T Sym. I th. M1
5 .. 100 sec
5 sec
Symmetry Iph: Pick-up
delay
8121
BAL. I LIMIT M2
1A
0.10 .. 1.00 A
0.50 A
Current Balance Monitor
Meas. Loc. 2
5A
0.50 .. 5.00 A
2.50 A
8122
BAL. FACT. I M2
0.10 .. 0.90
0.50
Bal. Factor for Curr.
Monitor Meas.Loc.2
8123A
T Sym. I th. M2
5 .. 100 sec
5 sec
Symmetry Iph: Pick-up
delay
8131
BAL. I LIMIT M3
1A
0.10 .. 1.00 A
0.50 A
Current Balance Monitor
Meas. Loc. 3
5A
0.50 .. 5.00 A
2.50 A
8132
BAL. FACT. I M3
0.10 .. 0.90
0.50
Bal. Factor for Curr.
Monitor Meas.Loc.3
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...