Security mechanisms in the command path ensure that a switch command can be
carried out only if the test of previously established criteria has been successfully com-
pleted. Additionally, user-defined interlocking conditions can be configured separately
for each device. The actual execution of the command is also monitored after its re-
lease. The entire sequence of a command is described briefly in the following.
Checking a
Command Path
Please observe the following:
• Command entry, e.g. using the keypad on the local user interface of the device
– Check password
→
access rights;
– Check switching mode (interlocking activated/deactivated)
→
selection of deac-
tivated interlocking status.
• User configurable interlocking checks:
– Switching authority;
– Device position check (set vs. actual comparison);
– Zone controlled / bay interlocking (logic using CFC);
– System interlocking (centrally via SICAM);
– Double operation (interlocking against parallel switching operation);
– Protection blocking (blocking of switching operations by protection functions);
– Circuit breaker synchronization check (synchronism check before a close com-
mand).
• Fixed commands:
– Internal process time (software watch dog which checks the time for processing
the control action between initiation of the control and final close of the relay con-
tact);
– Configuration in process (if setting modification is in process, commands are re-
jected or delayed);
– Equipment present as output;
– Output block (if an output block has been programmed for the circuit breaker, and
is active at the moment the command is processed, then the command is reject-
ed);
– Component hardware malfunction;
– Command in progress (only one command can be processed at a time for each
circuit breaker or switch);
– 1–of–n check (for multiple allocations such as common contact relays or multiple
protection commands configured to the same contact it is checked if a command
procedure was already initiated for the output relays concerned or if a protection
command is present. Superimposed commands in the same switching direction
are tolerated).
Command Execu-
tion Monitoring
The following is monitored:
• Interruption of a command because of a cancel command,
• Running time monitor (feedback monitoring time).
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...