3 Mounting and Commissioning
380
7UT613/63x Manual
C53000-G1176-C160-2
WARNING!
Warning of dangers evolving from improper primary tests
Non-observance of the following measure can result in death, personal injury or sub-
stantial property damage.
Primary tests may only be carried out by qualified persons who are familiar with com-
missioning protection systems, with managing power systems and the relevant safety
rules and guidelines (switching, earthing etc.).
3.3.1
Test Mode / Transmission Block
If the device is connected to a station control system or a server, the user is able to
modify, in some protocols, information that is transmitted to the substation (see Table
„protocol dependent functions“ in Appendix A.6).
If
test mode
is set ON, then a message sent by a SIPROTEC 4 device to the main
system has an additional test bit.This allows the message to be recognised as result-
ing from testing and not actual fault or power system event. Furthermore it can be de-
termined by activating the
Transmission block
that no indications at all are transmit-
ted via the system interface during test mode.
The SIPROTEC 4 System Description /1/ describes how to activate and deactivate
test mode and transmission block. Note that when DIGSI is being used, the program
must be in the
Online
operating mode for the test features to be used.
3.3.2
Test Time Synchronisation Interface
If external time synchronisation sources are used, the data of the time source (antenna
system, time generator) are checked (see Subsection 4 „Technical Data“ under „ Time
Synchronisation Interface“). A correct function (IRIG B, DCF77) is recognised in such
a way that 3 minutes after the startup of the device the clock status is displayed as
„synchronised“
, accompanied by the message
„Alarm Clock OFF“
.
Table 3-23
Time Status
No.
Status Text
Status
1
– – – – – – – –
Synchronised
2
– – – – – – ST
3
– – – – ER – –
Not synchronised
4
– – – – ER ST
5
– – NS ER – –
6
– – NS – – – –
Legend:
– – NS – – – –
– – – – ER – –
– – – – – – ST
Invalid time
Clock error
Summer time
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...