3 Mounting and Commissioning
386
7UT613/63x Manual
C53000-G1176-C160-2
Table 3-24
Indications on inconsistencies
Message
No
Meaning
see
Section
„Error1A/5Awrong“
192
Setting of the rated secondary currents on input/output board incon-
sistent, general
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„Err. IN CT M1“
to
„Err. IN CT M5“
30097
to
30101
Setting of the rated secondary currents inconsistent for the indicated
measured current input (3-phase inputs)
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„Err.IN CT1..3“
to
„Err.IN CT10..12“
30102
to
30105
Setting of the rated secondary currents inconsistent for the indicated
measured current input (inputs for single-phase busbar protection)
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„Err. IN CT IX1“
to
„Err. IN CT IX4“
30106
to
30109
Setting of the rated secondary currents inconsistent for the indicated
measured current input (single-phase inputs)
2.1.4
3.1.2 („Switch ele-
ments on printed
circuit boards“)
„FaultConfig/Set“
311
Group indication for configuration error
„GenErrGroupConn“
312
General: Error in transformer connection group
„GenErrEarthCT“
313
Error in single-phase inputs for earth fault differential protection
„GenErrSidesMeas“
314
Error in assignment of sides and/or measuring locations
„par too low:“
30067
Parameter setting value too small for the indicated address number
„par too high:“
30068
Parameter setting value too high for the indicated address number
„settingFault:“
30069
Parameter setting implausible for the indicated address number
„Diff Adap.fact.“
5620
The matching factor of the current transformers for the differential
protection is too great or too small
„Diff err. Set.“
5623
Differential protection setting not plausible
REF not avail.
5835
Restricted earth fault protection is not available for the configured
protected object
REF Adap.fact.
5836
The matching factor of the current transformers for restricted earth
fault protection is too great or too small.
REF Err CTstar
5830
There is no single-phase measuring input assigned to the starpoint
current for restricted earth fault protection
„REF err. Set.“
199.2493 Earth fault differential protection setting not plausible
„REF2 Not avail.“
205.2491 Restricted earth fault protection 2 is not available for the configured
protected object
„REF2 Adap.fact.“
205.2494 The matching factor of the current transformers for restricted earth
fault protection 2 is too great or too small.
„REF2 Err CTstar“
205.2492 There is no single-phase measuring input assigned to the starpoint
current for restricted earth fault protection 2
„REF2 err. Set.“
205.2493 Earth fault differential protection setting not plausible
O/C Ph. not active
1860
Time overcurrent protection for phase currents is not available for the
configured protected object
„O/C Para error“
023.2493 Settings for time overcurrent protection for phase currents not plausi-
ble
„O/C Ph2 Not av.“
207.2491 Time overcurrent protection for phase currents 2 is not available for
the configured protected object
„O/C Ph2 err Set“
207.2493 Settings for time overcurrent protection for phase currents 2 not plau-
sible
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...