3 Mounting and Commissioning
388
7UT613/63x Manual
C53000-G1176-C160-2
In the operational or spontaneous annunciations also check if there are any fault an-
nunciations from the device.
The matching factors of all measured value inputs are indicated in the operational an-
nunciations. It is recommended to check these factors even if none of the above men-
tioned alarms is present. The indicated factors are:
• generally, the ratio of the rated current/voltage of the side referred to the rated cur-
rent/voltage of the instrument transformers at the measuring locations;
• for differential protection, the ratio of the rated current of the protected object re-
ferred to the rated current of the current transformers at the measuring locations;
• For restricted earth fault protection, the ratio of the rated current of the assigned
side of the protected object referred to the rated current of the starpoint current
transformer.
None of these factors should be greater than 8 or smaller than 0.125. Otherwise, the
risk of higher measuring errors could arise. If a factor is greater than 50 or smaller than
0.02, unexpected reactions of protection function may occur.
„U< err. VT“
033.2492 Undervoltage protection is not available without voltage connection
„U< err. Set.“
033.2493 Undervoltage protection setting not plausible
„U> err. Obj.“
034.2491 Overvoltage protection is not available for the configured protected
object
„U> err. VT“
034.2492 Overvoltage protection is not available without voltage connection
„U> err. Set.“
034.2493 Overvoltage protection setting not plausible
„Freq. err. Obj.“
5255
Frequency protection is not available for the configured protected
object
„Freq. error VT“
5254
Frequency protection is not available without voltage connection
„Freq. err. Set.“
5256
Frequency protection setting not plausible
„Pr obj. error“
5101
Reverse power protection is not available for the configured protect-
ed object
„Pr CT Fact ><“
5099
The matching factor of the current transformers for reverse power
protection is too great or too small.
„Pr VT error“
5100
Reverse power protection is not available without voltage connection 2.12
„Pr set error“
5102
Reverse power protection setting not plausible
„Pf> Object err“
5132
Forward power supervision is not available for the configured protect-
ed object
„Pf> CT fact ><“
5130
The matching factor of the current transformers for forward power su-
pervision is too great or too small.
„Pf> VT error“
5131
Forward power supervision is not available without voltage connec-
tion
„Pf> set error“
5133
Forward power supervision setting not plausible
BrkFail not av.
1488
Breaker failure protection is not available for the configured protected
object
047.2493 Breaker failure protection setting not plausible
„BkrFail2 Not av“
206.2491 Breaker failure protection is not available for the configured protected
object
„BkrFail2 errSet“
206.2493 Breaker failure protection setting not plausible
„TripC ProgFail“
6864
For trip circuit supervision the number of binary inputs was set incor-
rectly
3.1
(„Connection Vari-
ants“)
Message
No
Meaning
see
Section
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...