3 Mounting and Commissioning
418
7UT613/63x Manual
C53000-G1176-C160-2
3.3.14 Stability Check and Triggering Oscillographic Recordings
In order to be able to test the stability of the protection during switchon procedures
also, switchon trials can also be carried out at the end. Oscillographic records obtain
the maximum information about the behaviour of the protection.
Prerequisite
Along with the capability of storing fault recordings via pickup of the protection func-
tion, the 7UT613/63x also has the capability of capturing the same data when com-
mands are given to the device via the service program DIGSI, the serial interface, or
a binary input. For the latter, event
„>Trig.Wave.Cap.“
must be allocated to a
binary input. Triggering of the recording then occurs, for example, via the binary input
when the protection object is energized.
An oscillographic recording that is externally triggered (that is, without a protective
element pickup or device trip) is processed by the device as a normal oscillographic
recording, and has a number for establishing a sequence. However, these recordings
are not displayed in the fault indication buffer, as they are not fault events.
Start Test Measure-
ment Recording
To trigger test measurement recording with DIGSI, click on
Test
in the left part of the
window. Double click in the list view the
Test fault recording
entry (see Figure 3-43).
Figure 3-43
Triggering oscillographic recording with DIGSI — example
Oscillographic recording is immediately started. During the recording, an annunciation
is output in the left area of the status line. Bar segments additionally indicate the
progress of the procedure.
The SIGRA or the Comtrade Viewer program is required to view and analyse the os-
cillographic data.
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...