4.1 General
427
7UT613/63x Manual
C53000-G1176-C160-2
Optical fibre (FO)
ST connector
FOC connector type
Connection for flush mounted
case
Rear panel, mounting location
„B“
Connection for surface
mounted case
in the inclined housing on the
case bottom
Optical wavelength
λ
= 820 nm
Laser class 1 according to EN
60825-1/-2
Using glass fibre 50/12
µ
m or
using glass fibre 62.5/125
µ
m
Permissible optical signal at-
tenuation
max. 8 dB using glass fibre
62.5/125
µ
m
Maximum bridgeable
distance
1.5 km
Character idle state
Selectable: factory setting
„Light off“
PROFIBUS RS485
(FMS and DP)
rear panel, mounting loca-
tion „B“,
9-pole DSUB miniature
socket
Connection for flush-mounted housing
Connection for surface
mounted case
in the inclined housing on the
case bottom
Test voltage
500 V; 50 Hz
Transmission speed
up to 1.5 MBd
Maximum bridgeable
distance
1,000 m (3300 ft) at
≤
93.75 kBd
500 m (1640 ft) at
≤
187.5 kBd
200 m (660 ft) at
≤
1.5 MBd
PROFIBUS FOC
(FMS and DP)
ST connector
with FMS: Single or double
ring according to order;
with DP: only double ring
available
FOC connector type
Connection for flush mounted
case
only with external OLM;
rear panel, mounting location
„B“
Connection for surface
mounted case
only with external OLM;
in the inclined housing on the
case bottom
Transmission speed
— recommended:
up to 1.5 MBd
> 500 kBd
Optical wavelength
λ
= 820 nm
Laser class 1 acc. to
EN 60825-1/-2
Using glass fibre 50/125
µ
m or
using glass fibre 62.5/125
µ
m
Permissible optical signal at-
tenuation
max. 8 dB, with glass fibre
62.5/125
µ
m
maximum bridgeable distance
between two modules at redun-
dant optical ring topology and
optical fibre 62.5/125 m
approx. 1.6 km (1750 ft) at
500 kbit/s
approx. 530 m (1750 ft) at
1500 kbit/s
DNP3.0 RS485
rear panel, mounting loca-
tion „B“,
9-pole DSUB miniature
socket
Connection for flush-mounted housing
Connection for surface
mounted case
in the inclined housing on the
case bottom
Test voltage
500 V; 50 Hz
Transmission speed
up to 19,200 Baud
Maximum bridgeable
distance
1 km
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...