4.1 General
431
7UT613/63x Manual
C53000-G1176-C160-2
EMC Tests for the Interference Emission (type test)
Irradiation with HF field, frequency sweep
IEC 60255-22-3; Class III
IEC 61000-4-3, Class III
10 V/m; 80 MHz to 1000 MHz;
10 V/m; 800 MHz to 960 MHz;
20 V/m; 1.4 GHz to 2.0 GHz;
80 % AM; 1 kHz
Irradiation with HF field, single frequencies
IEC 60255-22-3;
IEC 61000-4-3
– amplitude modulated
– pulse modulated
Class III: 10 V/m
80/160/450/900 MHz; 80 % AM; duty cycle
>10 s
900 MHz; 50 % PM, repetition frequency
200 Hz
Fast transient disturbance/burst
IEC 60255-22-4 and
IEC 61000-4-4, Class IV
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
repetition rate 300 ms; both polarities;
R
i
= 50
Ω
; test duration 1 min
High energy surge voltages (SURGE),
IEC 61000-4-5 Installation Class 3
—auxiliary voltage
Measuring inputs, binary inputs and relay out-
puts
impulse: 1.2/50
µ
common mode: 2 kV; 12
Ω
; 9
µ
F
Diff. mode:1 kV; 2
Ω
; 18
µ
F
common mode: 2 kV; 42
Ω
; 0. 5
µ
F
diff. mode: 1 kV; 42
Ω
; 0. 5
µ
F
Line conducted HF, amplitude modulated
IEC 61000-4-6, Class III
10 V; 150 kHz to 80 MHz: 80 % AM; 1 kHz
Power system frequency magnetic field
IEC 61000-4-8, Class IV
IEC 60255-6
30 A/m continuous; 300 A/m for 3 s; 50 Hz
0.5 mT; 50 Hz
Oscillatory surge withstand capability
IEEE Std C37.90.1
2.5 kV (peak value); 1 MHz;
τ
= 15
µ
s;
400 pulses per s; test duration 2 s; R
i
= 200
Ω
Fast transient surge withstand cap.
IEEE Std C37.90.1
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
Repetition rate 300 ms; both polarities;
R
i
= 50
Ω
; test duration 1 min
Damped oscillations
IEC 60694, IEC 61000-4-12
2.5 kV (peak value), polarity alternating
100 kHz, 1 MHz, 10 MHz and 50 MHz;
R
i
= 200
Ω
Standard:
EN 61000-* (generic standard)
Conducted interference, only power supply
voltage
IEC-CISPR 22
150 kHz to 30 MH
limit class B
Radio interference field strength
IEC-CISPR 22
30 MHz to 1000 MHz
Limit class B
Harmonic currents on the network lead at 230
V AC
IEC 61000-3-2
Class A limits are observed
Voltage fluctuations and flicker on the network
lead at 230 VAC
IEC 61000-3-3
Limits are observed
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...