2.1 General
47
7UT613/63x Manual
C53000-G1176-C160-2
The main protected object is a two-winding transformer YNd with an earthed starpoint
at the Y-side. Side
S1
is the upper voltage side (Y), side
S2
is the lower voltage side
(d). This definition of the sides for the main protected object (and only for it) is the basis
for the formation of the differential and restraint currents used in the differential pro-
tection.
For the side
S1
2 measuring locations
M1
and
M2
exist. The currents that are mea-
sured there belong to the side
S1
, their sum flowing on side 1 in the protected zone of
the main protected object. The position of the busbar isolator is not important here.
Likewise, the polarity of the currents is not yet considered under topology aspects.
At the lower voltage side, side
S2
also has two measuring locations because of its
branch point to the auxiliaries system circuit:
M3
and
M4
. The sum of these currents
flows into the low voltage side (
S2
) of the main protected object.
The 4 measuring locations
M1
to
M4
are assigned to the sides of the main protected
object, thus assigned measuring locations. They are the basis for the measured value
processing of three-phase currents for the differential protection. Basically, the same
applies to a single-phase transformer; Here, only the measured currents of the mea-
suring locations are connected in two-phase.
Measuring location
M5
is not assigned to the main protected object, but to the cable
feeder, which is not related in any way to the transformer.
M5
is thus a non-assigned
measuring location. The currents of this measuring location can be used for other pro-
tection functions, e.g. for 3-phase overcurrent protection for protection of the cable
feeder.
In 3-phase busbar protection there is no difference between measuring locations and
sides; both correspond with the feeders of the busbar.
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...