A Appendix
528
7UT613/63x Manual
C53000-G1176-C160-2
Figure A-17
Connection example 7UT613 for an auto-transformer bank with protected object auto-transformer branch-
points, with individually accessible earthing electrodes equipped with CTs (M3). The CTs on the earthing
side constitute a separate side for current comparison for each transformer of the bank. The starpoint of the
CTs at M3 is routed via an auxiliary input (
I
Z1
), which allows realisation of restricted earth fault protection
and/or earth overcurrent protection.