2.6 Dynamic Cold Load Pickup for Time Overcurrent Protection
193
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-83
Logic diagram for dynamic cold load pickup feature — illustrated for phase overcurrent protection stage on
side 1 (simplified)
2.6.2
Setting Notes
General
Dynamic cold load pickup can only be enabled if during configuration of the functional
scope was set at the address
117
COLDLOAD PICKUP
. =
Enabled
(see Subsection
2.1.3). If the function is not required
Disabled
is to be set. In address
1701
COLDLOAD PICKUP
the function can be set to
ON
or
OFF
.
Cold Load Criteria
You can determine the criteria for dynamic switchover to the cold load pickup values
for all protective functions which allow this switchover. Select the
current criterion
or
the breaker position criterion
breaker position
:
• address
1702
Start CLP Phase
for the phase current stages,
• address
1703
Start CLP 3I0
for the residual current stages,
• address
1704
Start CLP Earth
for the earth current.
The current criterion takes the currents of such side or measuring location to which the
corresponding protective function is assigned. When using the breaker position crite-
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...