2 Functions
218
7UT613/63x Manual
C53000-G1176-C160-2
heatup time of the object to be protected. There is the following connection between
the asymmetrical factor K and the cool-down time:
Example:
For asymmetry factor K = 20 s and a permanently permissible asymmetrical load of
I
2
/I
N
= 11 % a corresponding cool-down time is derived
This value does not depend on whether the respective values were set to secondary
values, as the current transformation ratios are reduced in numerator and denomina-
tor.
The I
2
>> stage can additionally be set as reserve stage for network faults, as de-
scribed above (margin heading „Definite Time Stages
I
2
>>,
I
2
> (O/C)“).
Note
The following applies to the parameter overview:
The current values
I
/
I
NS
refer to the rated current of the side to be protected of the main
protected object.
2.8.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
4001
UNBALANCE LOAD
OFF
ON
Block relay
OFF
Unbalance Load (Negative
Sequence)
4011
I2>>
1A
0.10 .. 3.00 A;
∞
0.50 A
I2>> Pickup
5A
0.50 .. 15.00 A;
∞
2.50 A
4012
I2>>
0.10 .. 3.00 I/InS;
∞
0.50 I/InS
I2>> Pickup
4013
T I2>>
0.00 .. 60.00 sec;
∞
1.50 sec
T I2>> Time Delay
4014
I2>
1A
0.10 .. 3.00 A;
∞
0.10 A
I2> Pickup
5A
0.50 .. 15.00 A;
∞
0.50 A
4015
I2>
0.10 .. 3.00 I/InS;
∞
0.10 I/InS
I2> Pickup
4016
T I2>
0.00 .. 60.00 sec;
∞
1.50 sec
T I2> Time Delay
4021
I2p
1A
0.10 .. 2.00 A
0.90 A
I2p Pickup
5A
0.50 .. 10.00 A
4.50 A
4022
I2p
0.10 .. 2.00 I/InS
0.90 I/InS
I2p Pickup
4023
T I2p
0.05 .. 3.20 sec;
∞
0.50 sec
T I2p Time Dial
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...