RTD-Boxes for Overload Detection
For thermal overload protection, taking into consideration the ambient or coolant tem-
perature as well as the overload protection with hot-spot calculation and relative
ageing rate determination, the coolant temperature in the protected object or the tem-
perature of the hottest spot of the winding (e.g. of a transformer) is required. At least
one resistance temperature detector (RTD) must be installed at the hot-spot location
which informs the device about this temperature via an RTD box 7XV5662-xAD. One
RTD box is able to process up to 6 RTDs. One or two RTD boxes 7XV5662-xAD can
be connected to the device.
2.10.1 Function Description
One RTD box 7XV5662-xAD can be used for up to 6 measuring points (RTDs) in the
protected object, e.g. in the transformer tank. The RTD box detects the coolant tem-
perature of each measuring point from the resistance value of the temperature detec-
tors (Pt 100, Ni 100 or Ni 120) connected with a two- or three-wire line and converts it
to a digital value. The digital values are output at the serial interface RS485.
One or two RTD boxes can be connected to the service interface of the 7UT613/63x.
Thus, up to 6 or 12 measuring points (RTDs) can be processed. For each temperature
detector, characteristic data as well as alarm (stage 1) and trip (stage 2) can be set.
The RTD box also acquires thresholds of each single measuring point. The informa-
tion is then passed on via an output relay. For further information, refer to the instruc-
tion manual of the RTD box.
2.10.2 Setting Notes
General
Set the type of temperature detector for RTD 1 (temperature sensor for measuring
point 1) at address
9011
RTD 1 TYPE
. You can choose between
Pt 100
Ω
,
Ni 120
Ω
and
Ni 100
Ω
. If no temperature detector is available for RTD 1, set
RTD 1 TYPE
=
Not connected
. This parameter can only be set with DIGSI under
Additional Set-
tings
.
Address
9012
RTD 1 LOCATION
informs the device regarding the mounting location
of RTD 1. You can choose between
Oil
,
Ambient
,
Winding
,
Bearing
and
Other
.
This parameter can only be set with DIGSI under
Additional Settings
.
Furthermore, in the 7UT613/63x an alarm temperature (stage 1) and a tripping tem-
perature (stage 2) can be set. Depending on the temperature unit selected in the
power system data in address
276
TEMP. UNIT
, the alarm temperature can be se-
lected in degree Celsius (
°
C) in address
9013
RTD 1 STAGE 1
or in degree Fahren-
heit (
°
F) in address
9014
RTD 1 STAGE 1
. The trip temperature expressed in Celsius
(
°
C) is set in address
9015
RTD 1 STAGE 2
, and under address
9016
RTD 1 STAGE
2
it can be set in degree Fahrenheit (
°
F) .
Temperature Detec-
tors
The setting options and addresses of all connected temperature detectors for the first
and the second RTD-box are listed in the following parameter overview.
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...