2.13 Forward Power Supervision
251
7UT613/63x Manual
C53000-G1176-C160-2
broken wire or voltage failure is recognised or voltage transformer protection breaker
failure (via the respective binary input) is indicated (see also Subsection "Technical
Data").
Figure 2-103
Logic diagram of the forward active power supervision
2.13.2 Setting Notes
General
The application of forward power monitoring is only possible in 3-phase protected ob-
jects. It can only be assigned to a side of the main protected object or another mea-
suring location. Furthermore, it is a prerequisite that the device is connected to a three-
phase voltage transformer set, that permits a sensible calculation of the active power
with the respective current transformer connection.
The forward power monitoring can only be effective and is only accessible if it has
been set during configuration under address
151
FORWARD POWER
=
Enabled
(sec-
tion 2.1.3).
Under address
5101
FORWARD POWER
the forward power monitoring can be switched
ON
or
OFF
. Furthermore, the command can be blocked during enabled monitoring
function (
Block relay
).
Pickup Values
For undershooting of a preset active power and the exceeding of another preset active
power, one pickup value each must be set.
If the forward power monitoring has been assigned to a side of the protected object,
the pickup value can be set directly as reference value (with reference to the nominal
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...