2.1 General
45
7UT613/63x Manual
C53000-G1176-C160-2
2.1.4
Power System Data 1
2.1.4.1
Topology of the Protected Object
Measured Value
Inputs
The devices of the 7UT613/63x family comprise various types with different function
facilities and different hardware scope which latter determines the number of available
analog inputs. Dependent on the ordering type, the following analog inputs are provid-
ed:
Table 2-1
Analog measuring inputs
1)
also applicable for single-phase power transformers
2)
selectable, contained in the number of 1-phase inputs
156
FREQUENCY Prot.
Disabled
Enabled
Disabled
Over / Underfrequency Protection
170
BREAKER FAILURE
Disabled
Enabled
Disabled
Breaker Failure Protection
171
BREAKER FAIL. 2
Disabled
Enabled
Disabled
Breaker Failure Protection 2
180
DISCON.MEAS.LOC
Disabled
Enabled
Disabled
Disconnect measurment location
181
M.V. SUPERV
Disabled
Enabled
Enabled
Measured Values Supervision
182
Trip Cir. Sup.
Disabled
2 Binary Inputs
1 Binary Input
Disabled
Trip Circuit Supervision
186
EXT. TRIP 1
Disabled
Enabled
Disabled
External Trip Function 1
187
EXT. TRIP 2
Disabled
Enabled
Disabled
External Trip Function 2
190
RTD-BOX INPUT
Disabled
Port C
Port D
Disabled
External Temperature Input
191
RTD CONNECTION
6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD simplex
Ext. Temperature Input Connec-
tion Type
Addr.
Parameter
Setting Options
Default Setting
Comments
Type
For 3-phase protected objects
For busbar 1-phase
Voltage
3-phase
Voltage
1-phase
Current
3-phase
Current (auxiliary)
Current
1-phase
Current (auxiliary)
1-phase
sensitive
1-phase
sensitive
7UT613
3
3
1
9
3
1
1
1
7UT633
3
3
1
9
3
1
1
1
7UT635
5
1
1
—
—
—
—
—
4
4
2
12
4
2
—
—
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...