2.1 General
63
7UT613/63x Manual
C53000-G1176-C160-2
forward power monitoring, the frequency protection, or for measuring tasks like the
display of voltages or the calculation and output of power and energy metering.
Figure 2-8 shows the various possible voltage assignments (which, of course do not
occur all at the same time in practice). Address
261
must be set to
VT SET
.
• For voltage measurement at
Ua
the voltages are measured on
Side 1
of the main
protected object.
• For voltage measurement at
Ub
, the voltages at the
Measuring loc.2
are mea-
sured that are assigned to side 1 of the main protected object.
• For voltage measurement at
Uc
the voltages are measured at the
Busbar
(only
possible in busbar protection).
• For voltage measurement at
Ud
, voltages at the
Measuring loc.3
are measured
that are not assigned to the main protected object.
• For voltage measurement at
Ue
the voltages are measured on
Side 2
of the main
protected object.
As these examples show, you can select sides, busbars, assigned or non-assigned
measuring locations. In 1-phase busbar protection, voltages can only be measured on
the
Busbar
.
In practice, the voltage assignment depends therefore on the voltages which the
device is expected to receive and process. Of course, voltage transformers must be
installed at the appropriate locations and connected to the device.
Figure 2-8
Examples of measured voltage assignment
Voltage assignment:
Ua
Voltage is measured at side S1 of the main protected object (power transformer)
Ub
Voltage is measured at the measuring location M2, assigned to side 1 of the main pro-
tected object
Uc
Voltage is measured at a busbar
Ud
Voltage is measured at the non-assigned measuring location M3
Ue
Voltage is measured at side S2 of the main protected object (power transformer)
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...