Functions
2.6 Circuit breaker failure protection (optional)
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
130
2.6.4
Information List
No.
Information
Type of In-
formation
Comments
1401
>BF on
SP
>BF: Switch on breaker fail protection
1402
>BF off
SP
>BF: Switch off breaker fail protection
1403
>BLOCK BkrFail
SP
>BLOCK Breaker failure
1415
>BF Start 3pole
SP
>BF: External start 3pole
1424
>BF STARTonlyT2
SP
>BF: Start only delay time T2
1432
>BF release
SP
>BF: External release
1435
>BF Start L1
SP
>BF: External start L1
1436
>BF Start L2
SP
>BF: External start L2
1437
>BF Start L3
SP
>BF: External start L3
1439
>BF Start w/o I
SP
>BF: External start 3pole (w/o current)
1440
BkrFailON/offBI
IntSP
Breaker failure prot. ON/OFF via BI
1451
BkrFail OFF
OUT
Breaker failure is switched OFF
1452
BkrFail BLOCK
OUT
Breaker failure is BLOCKED
1453
BkrFail ACTIVE
OUT
Breaker failure is ACTIVE
1461
BF Start
OUT
Breaker failure protection started
1472
BF T1-TRIP 1pL1
OUT
BF Trip T1 (local trip) - only phase L1
1473
BF T1-TRIP 1pL2
OUT
BF Trip T1 (local trip) - only phase L2
1474
BF T1-TRIP 1pL3
OUT
BF Trip T1 (local trip) - only phase L3
1476
BF T1-TRIP L123
OUT
BF Trip T1 (local trip) - 3pole
1493
BF TRIP CBdefec
OUT
BF Trip in case of defective CB
1494
BF T2-TRIP(bus)
OUT
BF Trip T2 (busbar trip)
1495
BF EndFlt TRIP
OUT
BF Trip End fault stage
1496
BF CBdiscrSTART
OUT
BF Pole discrepancy pickup
1497
BF CBdiscr L1
OUT
BF Pole discrepancy pickup L1
1498
BF CBdiscr L2
OUT
BF Pole discrepancy pickup L2
1499
BF CBdiscr L3
OUT
BF Pole discrepancy pickup L3
1500
BF CBdiscr TRIP
OUT
BF Pole discrepancy Trip
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...