Technical Data
4.7 Monitoring Functions
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
255
Trip Circuit Monitoring
Phase angle positive sequence power
Message when the angle lies inside the area of the P-Q level
parameterised by
ϕ
A and
ϕ
B.
-
ϕ
A,
ϕ
B
0° to 259°
Increments 1°
-
I
1
for
I
N
= 1 A 0.05 A to 2.00 A
Increments 0.01 A
for
I
N
= 5 A 0.25 A to 10.00 A
Increments 0.01 A
- U1
2 V to 70 V
Increments 1 V
Response Time
Approx. 30 ms
Number of monitored circuits
1 to 3
Operation per circuit
With 1 binary input or with 2 binary inputs
Pickup and Dropout Time
Approx. 1 to 2 s
Settable delay time for operation with 1 binary input
1 s to 30 s
Increments 1 s