Appendix
A.6 Functional Scope
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
285
A.6
Functional Scope
Addr.
Parameter
Setting Options
Default Setting
Comments
103
Grp Chge OPTION
Disabled
Enabled
Disabled
Setting Group Change Option
106
VT CONNECTION
3phase
1phase
NO
3phase
Voltage transformer connection
107
CT CONNECTION
YES
NO
YES
Current transformer connection
110
Trip mode
3pole only
1-/3pole
3pole only
Trip mode
126
Back-Up O/C
Disabled
TOC IEC
TOC ANSI
TOC IEC /w 3ST
Disabled
Backup overcurrent
133
Auto Reclose
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Disabled
Auto-Reclose Function
134
AR control mode
Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Trip w/ Tact
Auto-Reclose control mode
135
Synchro-Check
Disabled
Enabled
Disabled
Synchronism and Voltage Check
137
U/O VOLTAGE
Disabled
Enabled
Disabled
Under / Overvoltage Protection
139
BREAKER FAILURE
Disabled
Enabled
enabled w/ 3I0>
Disabled
Breaker Failure Protection
140
Trip Cir. Sup.
Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Disabled
Trip Circuit Supervision
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...