Appendix
A.7 Settings
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
289
2942
ϕ
B
Measurem.Superv
0 .. 359 °
340 °
Limit setting PhiB
2943
I1>
Measurem.Superv
1A
0.05 .. 2.00 A
0.05 A
Minimum value I1>
5A
0.25 .. 10.00 A
0.25 A
2944
U1>
Measurem.Superv
2 .. 70 V
20 V
Minimum value U1>
3401
AUTO RECLOSE
Autoreclosure
OFF
ON
ON
Auto-Reclose function
3402
CB? 1.TRIP
Autoreclosure
YES
NO
NO
CB ready interrogation at 1st trip
3403
T-RECLAIM
Autoreclosure
0.50 .. 300.00 sec
3.00 sec
Reclaim time after successful AR
cycle
3403
T-RECLAIM
Autoreclosure
0.50 .. 300.00 sec; 0
3.00 sec
Reclaim time after successful AR
cycle
3404
T-BLOCK MC
Autoreclosure
0.50 .. 300.00 sec; 0
1.00 sec
AR blocking duration after
manual close
3406
EV. FLT. RECOG.
Autoreclosure
with PICKUP
with TRIP
with TRIP
Evolving fault recognition
3407
EV. FLT. MODE
Autoreclosure
blocks AR
starts 3p AR
starts 3p AR
Evolving fault (during the dead
time)
3408
T-Start MONITOR
Autoreclosure
0.01 .. 300.00 sec
0.20 sec
AR start-signal monitoring time
3409
CB TIME OUT
Autoreclosure
0.01 .. 300.00 sec
3.00 sec
Circuit Breaker (CB) Supervision
Time
3410
T RemoteClose
Autoreclosure
0.00 .. 300.00 sec;
∞
∞
sec
Send delay for remote close
command
3411A
T-DEAD EXT.
Autoreclosure
0.50 .. 300.00 sec;
∞
∞
sec
Maximum dead time extension
3425
AR w/ BackUpO/C
Autoreclosure
YES
NO
YES
AR with back-up overcurrent
3430
AR TRIP 3pole
Autoreclosure
Autoreclosure
YES
NO
YES
3pole TRIP by AR
3431
DLC or RDT
Autoreclosure
WITHOUT
RDT
DLC
WITHOUT
Dead Line Check or Reduced
Dead Time
3433
T-ACTION ADT
Autoreclosure
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3434
T-MAX ADT
Autoreclosure
0.50 .. 3000.00 sec
5.00 sec
Maximum dead time
3435
ADT 1p allowed
Autoreclosure
YES
NO
NO
1pole TRIP allowed
3436
ADT CB? CLOSE
Autoreclosure
YES
NO
NO
CB ready interrogation before re-
closing
3437
ADT SynRequest
Autoreclosure
YES
NO
NO
Request for synchro-check after
3pole AR
3438
T U-stable
Autoreclosure
Autoreclosure
0.10 .. 30.00 sec
0.10 sec
Supervision time for dead/ live
voltage
3440
U-live>
Autoreclosure
Autoreclosure
30 .. 90 V;
∞
48 V
Voltage threshold for live line or
bus
3441
U-dead<
Autoreclosure
Autoreclosure
2 .. 70 V
30 V
Voltage threshold for dead line or
bus
3450
1.AR: START
Autoreclosure
YES
NO
YES
Start of AR allowed in this cycle
3451
1.AR: T-ACTION
Autoreclosure
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3453
1.AR Tdead 1Flt
Autoreclosure
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3454
1.AR Tdead 2Flt
Autoreclosure
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3455
1.AR Tdead 3Flt
Autoreclosure
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3456
1.AR Tdead1Trip
Autoreclosure
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1pole trip
3457
1.AR Tdead3Trip
Autoreclosure
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3458
1.AR: Tdead EV.
Autoreclosure
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3459
1.AR: CB? CLOSE
Autoreclosure
YES
NO
NO
CB ready interrogation before re-
closing
3460
1.AR SynRequest
Autoreclosure
YES
NO
NO
Request for synchro-check after
3pole AR
3461
2.AR: START
Autoreclosure
YES
NO
NO
AR start allowed in this cycle
3462
2.AR: T-ACTION
Autoreclosure
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3464
2.AR Tdead 1Flt
Autoreclosure
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
Summary of Contents for Siprotec 7VK61
Page 8: ...Preface SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 8 ...
Page 14: ...Contents SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 14 ...
Page 316: ...Literature SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 316 ...
Page 328: ...Glossary SIPROTEC 7VK61 Manual C53000 G1176 C159 3 Release date 05 2009 328 ...